Basic parameters
- Rated voltage Ur 24kV
- Lightning impulse voltage 125kV
- Withstand voltage frequency vol. Ud 50 kV
- IP ratings IP4X
- Rated frequency fr 50Hz
- Rated current Ir 630A
- Rated short time withstand Ik 16kA
- Operating temperature range -5 ÷ 40ºC
- Rated peak withstand current 40kA
- Rated duration of short circuit tk 1s
- Class of resistance to internal arc IAC AFLR 16kA/1s